Calcoid

Wire Gauge (AWG) Calculator

Find the smallest AWG conductor that meets NEC ampacity and your voltage-drop limit. Copper or aluminum, single- or three-phase, 60/75/90 C insulation.

Wire gauge (AWG) calculator

A

Actual load current. For a continuous load, enter 125% of the expected current.

ft

Distance from panel to load. Round-trip is doubled internally.

V

Common: 12 V (auto, RV), 120 V (US branch), 240 V (US dryer/HVAC), 480 V (commercial).

%

NEC recommends 3% per branch, 5% total feeder + branch.

C

Used for resistance and voltage drop, not ampacity selection.

Use the lowest rating allowed by the conductor and both terminations. A 90 C conductor does not make a 75 C terminal a 90 C terminal.

Recommended wire

AWG 12

Smallest gauge that meets both the NEC ampacity and your voltage-drop limit.

Voltage drop (V)

3.3 V

Voltage drop (%)

2.75 %

NEC current limit

20 A

R per 1000 ft

1.6504 Ω

Power loss

66.02 W

OptionAWGDrop (V)Drop (%)NEC limitStatus
One size up (oversized)AWG 102.081.7330 AMeets both
One size down (marginal)AWG 145.254.3715 AUnder ampacity

Uses NEC Table 310.16 at 86 F (30 C), with no more than three current-carrying conductors, plus the general 240.4(D) small-conductor limits. It does not apply adjustment factors, special-use exceptions, or local amendments.

Wire Gauge Planning Reference

ConductorCommon circuit useSelection factors
14 AWG copperLighting branch circuitAmpacity and breaker
12 AWG copperGeneral receptacle circuitAmpacity and breaker
10 AWG copperHigher-load branch circuitAmpacity, distance, and breaker
8 AWG copperLarge appliance branch circuitAmpacity, distance, and terminals
6 AWG copperLarge appliance or short feederAmpacity, distance, and terminals

Frequently Asked Questions about the Wire Gauge (AWG) Calculator

How does this calculator pick a wire size?
It evaluates its built-in AWG candidates and returns the smallest supported cross-section that meets both the selected ampacity and voltage-drop limits. The ampacity values are a limited NEC Table 310.16 planning model at standard conditions. The separate conductor operating temperature adjusts resistance for the voltage-drop estimate. It does not cover every conductor, terminal, installation method, load characteristic, or local code rule.
Why does the voltage-drop limit force me to a larger wire than the ampacity table suggests?
Ampacity and voltage drop are separate checks. A conductor may carry the current safely yet have too much resistance over a long run, so meeting your drop limit can require a thicker wire. NEC informational guidance commonly uses 3% for a branch circuit and 5% for feeder plus branch circuit, but the applicable code and equipment requirements control the final design.
What is the difference between single-phase and three-phase voltage drop?
This calculator uses VD = 2 x length x current x resistance / 1000 for a single-phase two-wire circuit and VD = sqrt(3) x length x current x resistance / 1000 for a balanced three-phase circuit. Those resistance-only formulas omit reactance, power factor, harmonics, and imbalance, which can matter in real installations.
Why does aluminum need a thicker wire than copper for the same load?
Aluminum's resistivity is roughly 1.6 times copper's (16.94 vs 10.371 Ohm cmil/ft at 20 C), so the same AWG aluminum conductor has about 60% more resistance per foot. To keep voltage drop under the same percentage limit you usually step up one or two gauges, and you must also use connectors and lugs rated for aluminum.
Does this replace a licensed electrician for sizing a real circuit?
No. The calculator uses a limited ampacity table and simplified voltage-drop formulas. Real work may require adjustments for ambient temperature, conductor count, continuous loads, terminals, insulation, installation method, fault current, power factor, and local amendments. Have a qualified electrician verify the conductor and protection before installation.

Related Calculators

More calculators in "Tech"

See all 98 calculators in "Tech"